Features:
More accurate up to 0.1% on Vrms(voltage), Frequency: 0.01Hz
Meet standard: IEC61000-4-30 Class S
Phase: -180~180
Lart 5.6 inch TFT LCD 640*480 resolution
With USB and lan interface
Safety standard: IEC61010-1 ,Safety Degree: 600V CAT IV 1000V CAT III
Specification:
Selection Table | |
Model | PQAN7610 |
Standard compliance | IEC61000-4-30 Class A |
Volt Amp Hz | ● |
Dips and swell | ● |
Harmonics | ● 100th Max. |
Power and energy | ● |
Unbalance | ● |
Monitor | ● |
Inrush | ● |
Flicker | ● |
Transients | ● |
400Hz | ● |
Wave Recording | ● |
Sample rate | 163.84kS/s (50/60Hz) |
TF Card | 32GB |
Battery | Lithium ion, 7.4V 5200mAh |
GPS/Beidou time synchronization | ● (option) |
WIFI | ● |
Input Characteristics | |
Number of inputs | 4 (3 phase + neutral) DC coupling |
Voltage Inputs | |
Max. input voltage | 1000Vrms |
Max. peak measurement voltage | 6kV |
Input Impedance | 4MΩ |
Current Input | |
Type | Clamp or current transformer with mV output |
Input Range | depends on supplied current clamp |
Input Impedance | 50kΩ 100kΩ (SA2200) |
Sampling System | |
Resolution | 8 channels 16 bits AD |
Sampling Rate | 163.84kS/s (50/60Hz), 8 channels sample
synchronously (SA2200) |
Measurement | |||
Measurement Range | Resolution | Accuracy | |
Voltage/Current/Frequency | |||
Vrms(AC+DC) | 1 ~ 1000Vrms | 0.01Vrms | ±0.1% of nominal
voltage |
Vpk | 1 ~ 1400Vpk | 0.01Vpk | ±0.5% of nominal
voltage |
V(Crest Factor) | 1.0 ~ >2.8 | 0.01 | ±5% |
Arms(AC) 10mV/A 1mV/A 65mV/1000A (AC) |
|||
0~150A | 0.01A | ±0.1%±0.1A | |
1~2000A | 0.01A | ±0.1%±0.1A | |
10~6000A | 0.01A | ±1%±2A | |
A(Crest Factor) | 1 ~ 10 | 0.01 | ±5% |
Frequency | 42.5~57.5(50Hz nominal) | 0.01Hz | ±0.01Hz |
51~69(60Hz nominal) | 0.01Hz | ±0.01Hz | |
320~480(400Hz nominal) | 0.01Hz | ±0.01Hz | |
Dips & Swells | |||
Vrms1/2 | 0 ~ 200% of nominal voltage | 0.01Vrms | ±0.2% |
Arms1/2 | depends on current clamps | 0.01A | ±1% |
Harmonic (IEC61000-4-7) | |||
Harmonic Number | 1 ~ 100(50/60Hz) (IEC61000-4-7) 1~12(400Hz) | ||
Harmonic Voltage %f | 0.0 ~ 100.0% | 0.01% | ±0.1% ± nx0.1% |
Harmonic Current %f | 0.0 ~ 100.0% | 0.01% | ±0.1% ± nx0.1% |
THD | 0.0 ~ 100.0% | 0.01% | ±2.5% |
Phase | -180° ~180 0° | 0.1° | ± nx0.1° |
Power and Energy | |||
P, S, Q1 | Max. 6000MW | 0.1kW | ±1%±10 digits |
PF & cosФ | 0 ~ 1 | 0.01 | ±0.1% |
kWh, kVAh, kvarh | depends on nominal voltage and current clamps | ±1%±10 digits | |
Flicker (IEC61000-4-15) | |||
Pst(10min)/Plt (2 hrs) | 0.00 ~ 20.00 | 0.01 | ±5% |
Unbalance | |||
Voltage | 0.0 ~ 20.0% | 0.1% | ±0.1% |
Current | 0.0 ~ 20.0% | 0.1% | ±1% |
Voltage Phase | -360° ~ 0° | 0.1° | ±0.1° |
Current Phase | -360° ~ 0° | 0.1° | ±0.5° |
Voltage Transient | |||
Vpk | ±6000Vpk | 1V | ±15% |
Vrms | 10 ~ 1000Vrms | 1V | ±2.5% |
Min. Test Time | 6.5us | ||
Inrush Current | |||
Arms | depends on current clamps | 0.01 | ±1% ± 5digits |
Inrush Duration | 1 ~ 32min selectable | 10ms | ±20ms |
Logger | |||
Recording | user-defined parameters for 4 phases at the same time | ||
Memory | Data stored in TF card, 32GB | ||
Duration Time | 2 hrs to 1 year, depends on the recording items and time interval | ||
Interval | 1s to 60 minutes |
CT clamps: (Option)
A: Range: 5A, Output Voltage Ratio: 10mV/A Accuracy: 0.2%
Working Frequency: 45Hz~55Hz Clamps Radius: 8mm
Size: 158*43*24mm
B: Range: 50A, Output Voltage Ratio: 10mV/A Accuracy: 0.2%
Working Frequency: 50Hz~400Hz Clamps Radius: 8mm
Size: 171*46*27mm
C: Range: 100A, Output Voltage Ratio: 10mV/A Accuracy: 0.2%
Working Frequency: 50Hz~400Hz Clamps Radius: 13mm
Size: 174*52*27mm
D: Range: 1A~1000A, Output Voltage Ratio: 1mV/A Accuracy: 1%
Working Frequency: 40Hz~100Hz Clamps Radius: 52mm
Size: 111*216*45mm
E: Flex type Primary Current Rating: 3000A , Output Voltage Ratio: 65mV/1000A
Range: 15A~3000A Accuracy: 1%+position Error
Maximum Allowable imput: 100KA Phase Error: Less than 1%
Noise: less than 2mVrms(10Hz~10Khz) Frequency Characteristic: 10Hz~10KHz(-3db)
Weight: 130g Length: 200cm CT perimeter: 50cm Postion Error: 2%
F: Flex type Primary Current Rating: 5000A , Output Voltage Ratio: 50mV/1000A
Range: 20A~1000A Accuracy: 1%+position Error
Maximum Allowable imput: 100KA Phase Error: Less than 1%
Noise: less than 2mVrms(10Hz~10Khz) Frequency Characteristic: 10Hz~10KHz(-3db)
Weight: 130g Length: 200cm CT perimeter: 50cm Postion Error: 2%
General | |
Batteries Inside | Lithium ion, 7.4V 5200mAh |
Characteristic | Dips and swell, Harmonic(IEC61000-4-30), Power and Energy |
Power Quality Analyzer Class A Energy Analyzer Harmonic Tester
- Product Code: PQAN-7620
- Availability: 2-3 Days
-
$3,328.00
Related Products